How To Install And Use Radar Level Meter Correctly
Leave a message
How to install and use radar level meter correctly
Radar level meter is a new type of liquid level instrument with high degree and non-contact continuous measurement. It can measure liquid level and slurry level by measuring radar wave conduction time. The temperature and pressure adaptability of radar level gauge is good, and its measurement is not affected by the volatility of the medium. The beam energy of the radar level meter is low, and it can work normally in the industrial frequency band, and has no harm to the human body and the environment. However, it must be combined with correct installation and use to obtain good measurement results. So, how should the radar level meter be properly installed and used?
First, the installation of radar level meter
If the container installed by the radar level meter is a concave container or a conical container, it should be noted that the radar beam of the radar level meter reaches the low point of the bottom of the tank when in use. If the liquid level is lower than this point, it cannot be measured. Therefore, the low point should be adjusted as far as possible during installation to ensure the accuracy of the measurement results.
The radar level meter should be installed at a distance of more than 200 mm from the container wall, and the installation distance between the radar level meter and the container wall should be about 1/6 of the diameter of the container. To avoid the radar level meter will receive multiple false echoes, which will interfere with the reception of normal signals, do not install the radar level meter above the intake pipe and in the center of the container.
During the installation process, if the proper distance between the radar level gauge and the container wall cannot be maintained due to the diameter of the container or other reasons, false echoes will occur when the distance between the container wall and the radar level gauge is small, and these false echoes should be stored during debugging to avoid errors in future use.
Second, the use of radar level meter
1. The measuring range of the radar level meter should be calculated from the time it touches the beam, but if the bottom of the tank of the radar level meter is concave, it should be calculated from its low point.
2, in the use of radar level gauge, in order to play the role of over-spill protection, should be set up a safe distance attached to the blind area.